Sometimes a solar power plant does not produce as much electricity as expected. This can be confusing, especially when the monitoring system shows that everything is working. In reality, the plant is losing power quietly. This is where I-V (Current–Voltage) curve testing becomes helpful. This case study shows how I-V curve testing helps identify actual problems in a solar power plant and how fixing them can improve its performance.
A large solar power plant was experiencing lower daily energy production compared with the designed output. All inverters were ON, SCADA showed normal operation without any alert signal, visually seemed that no major faults were there. But when compared to the plant design, the plant’s performance was lower than expected. In this situation the engineering team decided to look deeper and chose I-V curve testing to check the solar panels and the health of the electrical connections.
I-V curve testing is a medical check-up of a string. An I-V curve is a graph that shows Current (I) on the vertical axis and Voltage (V) on the horizontal axis. This test checks how much current the module produced, how much voltage it delivered and where it produces maximum power.
A healthy I-V curve is smooth, tall, wide, and has a sharp knee. Any results that deviate from the healthy smooth I-V curve serves as a warning sign. It means something is wrong, which could be associated with a variety of factors such as dirt on panels, loose connections, shading, or installation issues etc.
Identified the strings which are producing less power compared with the good strings. The good strings will be use as a reference. This will enable a comparison between “healthy” and “problematic” strings.
A portable testing device called PV Analyzer I-V Curve Tracer was connected to each string. Testing was done in a stable irradiance of at least 700 W/m² which is recommended, as per IEC 61829. Irradiance and module temperature were recorded while testing. These steps ensured that results are under the same conditions making them fair, meaningful and comparable.
The data are adjusted to STC using guidelines such as IEC 60891, so different strings could be compared accurately. A comparison is made between the healthy measured curves and the problematic curves.
The expectation is healthy strings show smooth and normal curves. However, the strings that didn’t exhibit these qualities may be interpreted as follows;
These issues were not visible in daily monitoring systems but were clearly exposed by I-V curve testing.
Based on the findings:
I-V curve testing is a detailed health check for a solar power plant. It helps identifies what is really happening inside the system, find hidden losses, and enables the right corrective actions to be implemented. When done properly and regularly, it improves reliability, energy production, and confidence in the plant’s long-term performance.